HVS-C-1523S In-Line Heat Shrinkable Splices (1/C Shielded Cable 15kV)
TE Connectivity’s (TE) Raychem 15 kV splice is for use with solid dielectric cables, including copper tape shielded, wire shielded, UniShield shielded, and lead sheath power cables.
This series of splices utilizes the triple-extrusion Rayfit splice sleeve, which provides high recovery forces resulting in superior interfacial pressure, reduced shrink and installation time, and a slimmer space saving profile.
Reliability, simple installations and cost effectiveness are key requirements to achieving a dependable network. Cable accessories using Rayfit components are excellent solutions to fulfill these requirements.
Key Features:
- The installed length of the kit is greatly reduced with the use of the Rayfit sleeve and a wraparound re-jacketing system reduces installed length

HVS-EG SPLICE EXTEND GROUND KIT (OPTIONAL, NOT INCLUDED)
PRODUCT SELECTION INFORMATION: DIMENSIONS IN INCHES (mm)
Part Number | Insulation Diameter (min.-max.) | Length of Moisture Blocked Braid | Braid Size (AWG) |
|---|---|---|---|
HVS-EG Splice Extend Ground Kit (optional, not included) | |||
1/C Cables 0.39 - 0.61 (10 - 16) | |||
0.30 - 1.25 (8 - 32) | 24 (610) | #8 | |
1.00 - 2.15 (25 - 55) | 24 (610) | #6 | |
1.55 - 3.40 (39 - 86) | 24 (610) | #4 | |
3/C cables 1.06 - 1.70 (27 - 43) | |||
0.30 - 1.25 (8 - 32) | 36 (914) | #8 | |
1.00 - 2.15 (25 - 55) | 36 (914) | #6 | |
1.55 - 3.40 (39 - 86) | 36 (914) | #4 | |
Ordering Information:
1. Select the appropriate catalog number. All selections are based on the typical dimensions for both 100 and 133% insulated cables, nominal insulation thickness 0.175-0.220.
2. Use the insulation OD, and jacket OD range as the final ordering criteria.
3. Kits can be installed with either aluminum or copper compression connectors (connectors not included with kit).
4. If external grounding, order an HVS-EG kit.
5. Standard package: 1 kit/box
6. Related test reports EDR-5440 for HVS-C and test report EDR-5444 for HVS-S, IEEE 404-2006 and IEEE-48 draft 2008 for 105°C of Splice and Terminations.
7. For AL Mechanical ShearBolt connector information request datasheet 9-1773440-4 and for CU request 165972.