In-Line Heat Shrink Transition Splice (15kV)
TE Connectivity’s (TE) HVSR “reducer” kits are used as a transition splice when the PILC/VCLC conductor size is much smaller than that of the poly cable. It can be used as an in-line splice for paper-insulated, lead-covered (PILC) cable or varnished cambric-insulated, lead-covered (VCLC) cable. It can also be used as a transition splice — PILC/VCLC to poly (copper tape, lead sheath, wire shield, UniShield, or jacketed/unjacketed concentric neutral) cable.
Key Features:
- Tested to the electrical and load cycling requirements of IEEE 404
- PILC splices utilize highly effective oil-stop systems
PRODUCT SELECTION INFORMATION: DIMENSIONS IN INCHES (MM)
Part # | Voltage | PILC/POLY Conductor Size (AWG/kcmil) | Insulation Diameter (min. - max.)- PILC | Insulation Diameter (min. - max.)- POLY | Connector Dimension- Both Cables OD | Connector Dimension- PILC/PILC Length | Connector Dimension- PILC/ POLY Length | Kit Installed Length | Required Installation Space |
|---|---|---|---|---|---|---|---|---|---|
HVS-1581D | 15 kV | #4 - 4/0 | 0.60 - 0.90 (15 - 23) | 0.65 - 1.05 (17 - 27) | 0.90 (23) | 3.5 (89) | 4.5 (114) | 31 (787) | 48 (1219) |