• Home
  • /
  • Shop
  • /
  • TE Connectivity Raychem HVT-82-G Medium Voltage Termination

TE Connectivity Raychem HVT-82-G Medium Voltage Termination

$257.03

Need it Sooner? Lead Time: In Stock, Ready to Ship.

HVT-82-G Medium Voltage Termination (HVT) 

5 kV - 35 kV

TE Connectivity’s (TE) Raychem HVT medium voltage termination system features a non-tracking, insulating surface that can withstand long-term electrical stress and surface pollution. The need for proven stress control is even more important at higher voltages. The materials used in TE’s HVT terminations are suitable for severely polluted areas and for all installation conditions, including top feed installation.

Reliable, field proven performance

Independent testing and field experience have repeatedly proven the long-term stability, durability and reliability of the HVT system, even in highly polluted environments. The non-tracking, insulating outer jacket can withstand the rigors of long-term electrical stress and surface pollution without loss of performance. TE’s non-tracking material offers the additional benefit of being maintenance free, with no need for periodic cleaning. Extensive load cycle testing verifies the long-term thermomechanical compatibility between the termination system and the cable.

Testing 

TE’s medium-voltage terminations are fully qualified per IEEE-48 as Class I terminations to provide a long, trouble-free service life.

Ease of installation

The HVT termination kits can be installed on all cable types without special adapters or accessories.

Key Features:

  • Broad range of standard indoor and outdoor kits for all plastic cable types, including armored cable 
  • Easy installation with a single technique which eliminates retraining-even on armored cable
  • HVT termination system may be installed upright or inverted and can bend to the same bending radius as the cable

Selection Information: Dimensions in Inches (Millimeters)

Part Number

Type of Kit

Conductor Size (Min.-Max.)- 5 kV (0.90")

Conductor Size (Min.-Max.)- 8 kV (0.115")

Insulation Diameter (Min.-Max.)

Jacket O.D. (Max.)

HVT-82-G

Indoor (5/8 kV)

300 kcmil – 500* kcmil

250 kcmil – 500 kcmi

0.80 – 1.25 (20 – 32)

1.50 (38)

Note:

*URD and LC kits are rated for 15 – 35 kV only; HVT-M kits for 5/8 – 25 kV only.

Weight 0.70 lbs
Dimensions 17 × 5 × 6 in